Carnot Maximum Thermodynamic Efficiency Formula

Carnot's theorem proves no heat engine operating between absolute temperatures T_H and T_C can exceed thermal efficiency η_max = 1 − T_C/T_H.

Formula Reference
Main Formula
η_max = 1 − (T_C / T_H) = W_out / Q_H
Rearranged Forms
COP_heating = T_H / (T_H − T_C)
COP_cooling = T_C / (T_H − T_C)
Variables & Units
Variables & Units — Carnot Maximum Thermodynamic Efficiency Formula
SymbolNameUnit
etaMaximum Carnot Efficiencyratio (0–1)
THHot Reservoir Temperature T_HK
TCCold Sink Temperature T_CK
Inputs & Parameters
[K]
[K]
Calculated Result (Maximum Carnot Efficiency)
eta =0.647059ratio (0–1)

Formula Notes & Background

  • A reversible cycle of two isotherms and two adiabats satisfies ΔS_cycle = Q_H/T_H − Q_C/T_C = 0 ⇒ Q_C/Q_H = T_C/T_H.
  • Since W = Q_H − Q_C, efficiency η = W/Q_H = 1 − Q_C/Q_H = 1 − T_C/T_H.

Step-by-Step Examples

#1: Steam turbine operating between superheated steam at T_H = 850 K and condenser cooling water at T_C = 300 K.
T_H = 850 KT_C = 300 K
η_max = 1 − (300 / 850) = 1 − 0.3529
→ η_max = 0.6471 (64.71% theoretical ceiling)
#2: Ideal heat pump delivering indoor heat at T_H = 295 K from outdoor air at T_C = 270 K.
T_H = 295 KT_C = 270 K
COP_max = 295 / (295 − 270) = 295 / 25
→ COP_max = 11.8 (real heat pumps achieve ~3.5–4.5)
Was this tool helpful?

Frequently Asked Questions

Can Carnot efficiency ever reach 100%?+

Only if T_C = 0 K (impossible by the Third Law of Thermodynamics) or T_H → ∞.

Why must T_H and T_C be in Kelvin?+

Thermodynamic entropy scales with absolute Kelvin temperature dS = δQ_rev/T; Celsius ratios produce physically meaningless numbers.

Why can a heat pump COP exceed 1.0 without violating energy conservation?+

Because electrical work moves existing ambient thermal energy Q_C from outdoors rather than generating all heat resistively: Q_H = W + Q_C.